Portable AC400V-108KW AC Resistive Load Bank For Generator Testing/ UPS testing
Portable AC400V-108KW AC Resistive Load Bank For Generator Testing/ UPS testing
b. The load overcomes the fact that the water resistance test system cannot accurately control the resistance value, the water is easy to boil, easy to scale, can not be subjected to sudden loading/depression load reduction test, and is difficult to control.It is an upgraded product of water resistance. This product has high safety, low maintenance cost, low noise and strong overload capability.
c. The fan adopts a small axial fan, with large wind volume, good heat dissipation, how noise and other characteristics.
1. Working environment conditions
1.1. Environmental temperature:- 10~+50℃;
1.2. Relative humidity: ≤ 90%;
1.3. Altitude: ≤ 2500m;
1.4. Seismic intensity: VIII degree;
1.5 Other conditions: limited to indoor use only, with no debris at a distance of ≥ 1 meter from the air inlet and outlet;
2. Rated electrical parameters
2.1 Rated voltage: AC230V/AC400V;
2.2. Rated current: AC400V/153A;
2.3 Rated power: R=108kW;
2.4 Frequency: AC50Hz/60Hz;
2.5 Power factor: PF=1;
2.6. Working power supply: AC85-264V or DC120-370V;
3. Technical indicators
3.1 Cooling method: forced air cooling;
3.2. Inlet and outlet direction: side inlet, side outlet;
3.3 Display mode: Touch screen displays voltage, current, power factor, frequency, active power, reactive power, etc;
3.4 Loading method: Power grading setting. Local touch screen control for loading/unloading; Customers can input the required power level according to their testing needs;
Power classification A/B/C: 100W, 200W, 200W, 500W, 1kW, 2kW, 2kW, 5kW, 10kW, 15kW;
3.5. Load accuracy: ± 5%;
3.6 Protection level: IP20;
3.7 Working mode: Can work continuously;
3.8 Fan noise: ≤ 80 decibels at a distance of 1 meter from the load;
3.9. Box frame: 400 * 600 * 825mm (width * depth * height);